A step-by-step technique has been implemented in the analytical study of heat transfer and pressure gradient characteristics of refrigerants R-410A, R-407C, R-22 and R-134a used as cooling media in the condenser of a steam power plant. Refrigerants are optimized to replace water/air as coolant in the condenser of a steam power plant. Refrigerants have much lower temperatures and much higher heat transfer rates than water or air. The thermal resistances that affect heat transfer characteristics and surface condenser performance are included. The effect of inlet refrigerant temperature and mass flow rate are reported for the four refrigerants. Calculations are performed at two inlet refrigerant temperatures −21 °C and −30 °C and mass flow rate ranging from 92.905 to 132.905 kg/s. The results revealed that the overall heat transfer coefficient, heat transfer rate and condensation rate increased with refrigerant mass flow rate, with higher values at lower inlet refrigerant temperatures. For a given refrigerant mass flow rate and inlet temperature, the analytical study indicated that R-410A has higher values of overall heat transfer coefficient, heat transfer rate and condensation rate than R-407C, R-22 and R-314a, respectively. Moreover, it is found that R-410A, at −30 °C and 132.905 kg/s, is superior in condensing all steam entering the condenser than the other refrigerants; this corresponds to higher exergy efficiency. The condenser pressure was observed to be slightly higher for R-410A than the other refrigerants.
Skip Nav Destination
ASME Turbo Expo 2014: Turbine Technical Conference and Exposition
June 16–20, 2014
Düsseldorf, Germany
Conference Sponsors:
- International Gas Turbine Institute
ISBN:
978-0-7918-4573-8
PROCEEDINGS PAPER
Comparative Study of Using R-410A, R-407C, R-22 and R-134a as Cooling Medium in the Condenser of a Steam Power Plant
Khaled Yousef,
Khaled Yousef
Menoufia University, Menoufia, Egypt
Search for other works by this author on:
Abebayehu Assefa,
Abebayehu Assefa
Addis Ababa University, Addis Ababa, Ethiopia
Search for other works by this author on:
Ahmed Hegazy,
Ahmed Hegazy
Menoufia University, Menoufia, Egypt
Search for other works by this author on:
Abraham Engeda
Abraham Engeda
Michigan State University, East Lansing, MI
Search for other works by this author on:
Khaled Yousef
Menoufia University, Menoufia, Egypt
Abebayehu Assefa
Addis Ababa University, Addis Ababa, Ethiopia
Ahmed Hegazy
Menoufia University, Menoufia, Egypt
Abraham Engeda
Michigan State University, East Lansing, MI
Paper No:
GT2014-25033, V05CT20A001; 12 pages
Published Online:
September 18, 2014
Citation
Yousef, K, Assefa, A, Hegazy, A, & Engeda, A. "Comparative Study of Using R-410A, R-407C, R-22 and R-134a as Cooling Medium in the Condenser of a Steam Power Plant." Proceedings of the ASME Turbo Expo 2014: Turbine Technical Conference and Exposition. Volume 5C: Heat Transfer. Düsseldorf, Germany. June 16–20, 2014. V05CT20A001. ASME. https://doi.org/10.1115/GT2014-25033
Download citation file:
7
Views
0
Citations
Related Proceedings Papers
Related Articles
Comparative Study of Using R-410A, R-407C, R-22, and R-134a as Cooling Medium in the Condenser of a Steam Power Plant
J. Eng. Gas Turbines Power (February,2015)
Exergy Analysis of Condensation of a Binary Mixture With One Noncondensable Component in a Shell and Tube Condenser
J. Heat Transfer (August,2008)
Measurement of Condensation Heat Transfer Coefficients at Near-Critical Pressures in Refrigerant Blends
J. Heat Transfer (August,2007)
Related Chapters
Engineering and Physical Modeling of Power Plant Cooling Systems
Thermal Power Plant Cooling: Context and Engineering
Combined Cycle Power Plant
Energy and Power Generation Handbook: Established and Emerging Technologies
Introduction
Thermal Power Plant Cooling: Context and Engineering